N.Y. ADC. LAW § 27-375 : NY Code - Section 27-375: Interior stairs
Search N.Y. ADC. LAW § 27-375 : NY Code - Section 27-375: Interior stairs
Interior stairs shall comply with the
following requirements:
(a) Capacity. The capacity of interior stairs shall be as listed in
table 6-1.
(b) Width. The width of interior stairs shall be the clear width
between walls, grilles, guards, or newel posts. Stair stringers may
project into the required width not more than two inches on each side of
the stair. No interior stair shall be reduced in width in the direction
of exit travel. Interior stairs shall be at least forty-four inches wide
except as follows:
(1) Interior stairs may be not less than thirty-six inches wide when
serving not more than thirty occupants per stair on any floor in
buildings classified in occupancy groups J-1 and J-2 or when serving
buildings classified in occupancy group J-3 and exceeding four stories
in height, or when serving not more than sixty occupants per stair on
any floor in buildings classified in occupancy groups E, B, and D.
(2) Interior stairs may be not less than thirty inches wide when
serving mezzanines having an occupant load not exceeding twenty-five
persons or when located in buildings classified in occupancy group J-3
not more than three stories in height. Interior stairs in four story
buildings classified in occupancy group J-3 shall be a minimum of
thirty-three inches in width.
(c) Headroom. The clear headroom shall be at least seven feet, except
that in buildings classified in occupancy groups J-2 and J-3, the
minimum clear headroom may be six feet eight inches. Headroom in a
flight of stairs shall be measured vertically between two parallel
inclined planes, one of which contains the line of the nosing or upper
front edge of each tread and extends to its intersection with a landing
and the other of which is through any point directly above the first
plane that limits the headroom of the stair.
(d) Landings and platforms. Landings and platforms shall be provided
at the head and foot of each flight of stairs, except at the head of
basement stairs in one- and two-family dwellings, and shall comply with
the following:
(1) The minimum width of landings and platforms perpendicular to the
direction of travel shall be equal to at least the width of the stairs
except that on a straight-run stair, the distance between risers of
upper and lower flights at intermediate landings or platforms need not
be more than forty-four inches.
(2) The maximum vertical rise of a single flight of stairs between
floors, between landings or platforms, or between a floor and a landing
or platform shall not exceed eight feet in buildings classified in
occupancy groups F and H, and twelve feet in all other occupancy groups.
No flight of stairs shall have less than two risers.
(3) Landings and platforms shall be enclosed on sides by walls,
grilles or guards at least three feet high.
(e) Risers and treads. Risers and treads shall comply with table 6-4
and with the following:
(1) The sum of two risers plus one tread exclusive of nosing shall be
not less than twenty-four nor more than twenty-five and one-half inches.
(2) Riser height and tread width shall be constant in any flight of
stairs from story to story.
(3) Winders shall not be permitted in required exit stairs except in
one- and two-family dwellings and except as permitted in subdivision l
of this section. The width of winder treads when measured eighteen
inches from the narrower end shall be at least equal to the width of
treads above or below the winding section.
(4) Curving or skewed stairs may be used as exits when the tread and
riser relationship is in accordance with table 6-4 when measured at a
point eighteen inches in from the narrow end of the tread; and no tread
shall be more than three inches narrower or three inches wider at any
point than the width established eighteen inches in from the narrow end.
(f) Guards and handrails. Stairs shall have walls, grilles, or guards
at the sides and shall have handrails on both sides, except that stairs
less than forty-four inches wide may have a handrail on one side only.
Handrails shall provide a finger clearance of one and one-half inches,
and shall project not more than three and one-half inches into the
required stair width.
(1) Stairs more than eighty-eight inches wide shall have intermediate
handrails dividing the stairway into widths that maintain the nominal
multiples of twenty-two inches, but the widths shall not be greater than
eighty-eight inches nor less than forty-four inches.
(2) The height of handrails above the nosing of treads shall be not
more than thirty-four inches nor less than thirty inches.
(3) Handrails shall be returned to walls and posts when terminated,
except in one- and two-family dwellings.
(4) Handrails shall be designed to support loads in compliance with
the requirements of subchapter nine of this chapter.
(5) Handrails in all stairs shall be of materials having a
flame-spread rating not exceeding one hundred fifty.
(g) Stair doors. Doors providing access to stairs shall comply with
the requirements of subdivision (a) of section 27-342 of article five of
subchapter five of this chapter and subdivision (e) of section 27-371 of
this article. The swing of stair doors shall not block stairs or stair
landings, nor shall any door at any point of its swing reduce the
effective width of the landing or stair to less than seventy-five
percent of the required width of the landing or stair, or to less than
the width of the door opening on them. The width of doors from a stair
shall not be less than the number of units of exit width required for
the capacity of the stair, but in no case shall the door width be less
than required by subdivision (e) of section 27-371 of this article.
(h) Stair construction. Risers, treads, stringers, landings,
platforms, and guards, exclusive of handrails, shall be built of
noncombustible materials except that interior stairs in buildings of
construction group II may be built of combustible materials in buildings
classified in occupancy group B-2, C, D or E when the buildings are two
stories in height or less, and in buildings classified in occupancy
group J-2 or J-3 when the buildings are not more than three stories in
height, and in the case of J-2 occupancy group, when occupied by not
more than three families. Interior stairs shall have solid treads. All
risers shall be closed except as otherwise provided in subdivision (i)
of this section. When of combustible construction, the soffit of
interior stairs shall be fire protected by material having a minimum
fire resistive rating of one hour or five-eighths inches gypsum wall
board or equivalent, or the space beneath shall be enclosed without
openings by material having a one hour fire resistance rating unless
permitted to have open risers by subdivision (i) of this section. Where
two separate interior stairs are contained within the same enclosure (so
called "scissor stairs"), each stair shall be separated from the other
by noncombustible construction having a fire resistance rating equal to
that required for the stair enclosure.
Stairs, platforms, and landings shall be designed to support all loads
in compliance with the requirements of subchapter nine of this chapter.
Treads and landings shall be built of or surfaced with nonskid
materials.
(i) Stair enclosures.
(1) Interior stairs shall be enclosed with construction complying with
the requirements of table 3-4 except that:
(a) In buildings three stories or less in height excluding those
classified in occupancy group J-1 or J-2 combustible construction group
II, the enclosing construction may have a one hour fire resistant
rating.
(b) Stairs in buildings or spaces classified in occupancy group J-3
and not more than three stories in height, need not be enclosed except
as otherwise required in subdivision (a) of section 27-341 of article
five of subchapter five of this chapter. Stairs may have open risers in
one family dwellings and group homes.
(c) Unenclosed stairs in buildings classified in assembly occupancy
group F may be permitted as provided in subchapter eight of this
chapter.
(d) Stairs from floors or mezzanines may be unenclosed, with open or
closed risers.
(e) In buildings classified in occupancy group J-2 occupied
exclusively by not more than one family on each story without boarders,
roomers or lodgers and not more than three stories in height, the
enclosing construction may have a one hour fire-resistance rating which
may be constructed of combustible material provided that the stair
enclosure is protected with an automatic sprinkler system complying with
the construction provisions of subchapter seventeen of this chapter.
(f) In buildings classified in occupancy group J-1 or J-2 not more
than two stories in height of combustible construction group II, the
enclosing construction may have a one hour fire-resistance rating which
may be constructed of combustible material; however, where only one
vertical exit is provided the stair enclosure shall be protected
throughout with an automatic sprinkler system constructed in accordance
with the provisions of subchapter seventeen of this chapter.
(g) Except as provided in subparagraphs (a), (e) and (f) of this
paragraph, in all buildings or spaces classified in occupancy group J-1
or J-2, the enclosing construction shall be of masonry or an approved
equivalent material having at least a two hour fire-resistant rating.
(2) Access stairs connecting not more than two stories which do not
serve as a required exit may be constructed without an enclosure in
buildings classified in other than occupancy group H-2. Such stairs
shall be additional to and shall not obstruct or interfere with required
exit facilities. When the first story below grade is served by an
interior, unenclosed access stair, it shall be sprinklered in accordance
with the construction provisions of subchapter seventeen of this
chapter.
(3) The interior finish of interior stair enclosures shall be in
accordance with the requirements of table 5-4.
(4) Stair enclosures shall be vented in accordance with the
requirements for shafts in subdivision (d) of section 27-344 of article
five of subchapter five of this chapter except that stair enclosures for
buildings or spaces classified in occupancy group J-1 or J-2 shall be
vented as follows:
a. In occupancy group J-2 buildings three stories in height and with
not more than one dwelling unit per story or two stories in height with
not more than two dwelling units per story, shall be provided with a
skylight at least nine square feet in area, glazed with plain glass with
a wire screen over and under and provided with fixed or movable
ventilators having a minimum open area of forty square inches.
b. In occupancy group J-1 or J-2 buildings two stories in height with
more than two dwelling units per story shall be provided with a skylight
of at least twenty square feet in area, glazed with plain glass, with a
wire screen over and under and provided with fixed or movable
ventilators having a minimum open area of forty square inches.
c. In occupancy group J-1 buildings exceeding two stories in height
and in occupancy group J-2 buildings three stories in height with more
than one dwelling unit per story or exceeding three stories in height
shall be provided with a skylight at least twenty square feet in area,
glazed with plain glass with a wire screen over and under and provided
with fixed or movable ventilators having a minimum open area of one
hundred forty-four square inches. In lieu of the skylight and
ventilators a window of equal area may be provided with fixed louvres
having a minimum open area of one hundred forty-four square inches
installed in or immediately adjacent to the window.
(5) When dwelling units are located over a space classified in
occupancy group C or E on the street floor, they shall be provided with
a separate enclosed interior stair, or with an exterior stair.
(6) Impact resistance. Stair enclosures serving occupancy group E
spaces (office spaces) in high rise buildings constructed pursuant to
applications filed on or after July 1, 2006 shall comply with rules to
be promulgated by the commissioner establishing minimum impact
resistance standards. Such rules shall permit compliance with assemblies
comprising approved reinforced construction boards affixed onto stud
framing. The commissioner shall promulgate such rules on or before
January 1, 2006.
(j) Openings and obstructions to stair enclosures. No piping of any
kind, with the exception of piping required or permitted in subchapter
seventeen of this code, shall be permitted within a stair enclosure. No
openings of any kind, other than windows, fire department access panels,
exit doors and openings specifically authorized in reference standard RS
5-18 shall be permitted within a stair enclosure. Pipes required or
permitted by such subchapter seventeen and protected in accordance
therewith which do not reduce the required clearances of the enclosure
may be permitted. Ducts protected in accordance with the requirements of
subchapter thirteen of this chapter, which do not reduce the required
clearances of the enclosure, may be permitted. In addition, in buildings
in occupancy group J-2, which are three stories or less in height and
occupied by not more than two families on each story, a door from an
apartment may open directly into a stair, and the door may swing into
the apartment.
(k) Roof access. (1) Except as otherwise provided for in paragraphs
two and three of this subdivision, in buildings or in building sections
more than three stories or forty feet high with roofs having a slope of
less than twenty degrees, access to the roof shall be provided by at
least one interior stair, except that access to setback roof areas may
be through a door or window opening to the roof. Interior stairs
extending to roofs shall be enclosed in bulkheads of fire-resistant
construction meeting the requirements of subchapter five of this
chapter.
(2) In buildings or in building sections classified in occupancy group
J-1 or J-2 more than two stories in height, except as otherwise provided
for in paragraph three of this subdivision, with roofs having a slope of
fifteen degrees or less all interior stairs, except those terminating at
a level of a setback roof, shall extend to the roof and shall be
enclosed in bulkheads of fire-resistive construction meeting the
requirements of subchapter five of this chapter. Stairs terminating at
the level of a setback shall provide access to the setback roof areas
through a door except where the setback is less than four feet in width,
measured from the inside of the parapet wall, and less than ten feet in
length.
(3) In buildings or in building sections classified in occupancy group
J-1 or J-2 two stories in height and in occupancy group J-2 three
stories in height with not more than one dwelling unit per story with
roofs having a slope of fifteen degrees or less, access to the roof
shall be provided through a scuttle at least twenty-one inches in width
and twenty-eight inches in length and shall comply with subdivision (c)
of section 27-338 of article four of subchapter five of this chapter.
Scuttles shall be located within each stair enclosure with a stationary
iron ladder leading thereto.
(l) Spiral stairs. Spiral stairs may serve as access stairs between
two floors or levels in accordance with the provisions of paragraph two
of subdivision (i) of this section. Such stairs may not serve as
required exits, except that unenclosed spiral stairs when built of
noncombustible materials and having a tread length of at least thirty
inches may serve as exits from mezzanines or balconies having an
occupant load not exceeding twenty-five persons.
Table 6-4 Maximum Riser Height and Minimum Tread Width
========================================================================
Occupancy Group Classification Maximum Riser Minimum Tread{1}
of Building Height (in.) Width (in.)
------------------------------------------------------------------------
Residential J-3 (with closed risers).. 8 1/4 9 plus 1 1/4 nosing
Residential J-3 (with open risers).... 8 1/4 9 plus 1/2 nosing
Residential J-2 (with only three......
dwelling units)....................... 8 1/4 9 plus 1 1/4 nosing
Assembly F............................ 7 1/2 9 1/2 plus nosing
Institutional H-2..................... 7 10 plus nosing
All others{2}......................... 7 3/4 9 1/2 plus nosing
========================================================================
Notes:
{1} Treads may be undercut a distance equal to the nosing. A nosing
shall not be required when tread width is eleven inches or wider.
{2} The proportions and dimensions of treads and risers may be
adjusted in buildings classified in occupancy group G to suit the age of
occupants, subject to the approval of the commissioner.